Producing reliable power from 1000 kVA to 1400 kVA ekW at 50 Hz, our 3512 diesel generator sets are engineered for your mission critical, continuous, standby and prime applications. Each meet ISO 8528-5 transient response requirements and accept 100 percent rated load in one. And each is designed for low fuel consumption reducing operating costs. Our integrated control system, including Cat® UPS, ATS and switchgear, secure your power supply and keep you connected to your fleet through on-site and remote monitoring. Our EMCP4 control panel provides a flexible control platform, with an easy-to-use display — it’s your single source for management and diagnostics tools. We know it’s not just quality that matters but customization. Choose from a broad range of accessories and bolt-on system expansion attachments. Find flexible packaging options to work with your spatial restrictions and environment conditions.
Rating | 1150kVA,1275kVA, |
Voltage | 400 /230 V |
Frequency | 50 Hz |
Speed | 1500 rpm |
Cat Diesel Engine
Generator
Cat EMCP Control Panel
The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further customized to meet your needs through programming and expansion modules.
Design Criteria
The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient response.
UL 2200 / CSA – Optional
Single-Source Supplier
Fully prototype tested with certified torsional vibration analysis available
World Wide Product Support
Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products
3512A (50 Hz) Standard Equipment
Air Inlet
Cooling
Exhaust
Fuel
Generator
Power Termination
Control Panel
General
3512A (50 Hz) Optional Equipment
Exhaust
Generator
Power Termination
Control Panels
Mounting
Starting/Charging
General
Selection of right Construction Equipment for your Project